+31(0)174-671 800
PROFINET IO Device
101-220110

PROFINET IO Device

The ComBricks PROFINET Device enables the largest multiple cross gateway between other PROFINET and PROFIBUS modules which are placed in the backplane. Simultaneously, the PLC/DCS system that has the PROFINET Device in Data Exchange can access inserted I/O modules.

Request offer

Introduction

The ComBricks PROFINET Device enables the largest multiple cross gateway between other PROFINET and PROFIBUS modules which are placed in the backplane. Simultaneously, the PLC/DCS system that has the PROFINET Device in Data Exchange can access inserted I/O modules.

It's the component of choice to establish communication between multiple PROFINET and PROFIBUS controllers that manage their own specific network. The gateway works the same way as regular DP/DP and PN/DP couplers. The data area between the modules is customized with the help of some pre-defined blocks from the GSD files. ComBricks has the advantage that 10 PROFINET / PROFIBUS modules can exchange information.

The configuration steps are the same as any other PROFINET device. By means of the GSD file the respective I/O modules have to be selected in the configuration tool, after which the PLC can make the I/Os available for the software application and the network.

Application areas

null null

 

UL-listed

This product is UL-listed. Read more about UL-certification.

 

Technical specifications

PROFINET

  • Version 2.25 - Conformance class B
  • Certification number: ZZ10500
  • Ident Number: 0x4000 hex - 0x0001 hex
  • 1 ms - 1 .. 128 input or output bytes
  • 1024 Bytes input and 1024 bytes output (204 Bytes per module)
  • DeviceName by DCP or hardware rotary switch
  • Transferrable bytes to proxies (inputs and outputs): 1, 2, 3, 4, 8, 12, 16, 20, 24, 28, 32, 64, 96, 128, 160, 192, 204

Ethernet

  • 10/100 Mbps (100BaseTX, 10BaseT)
  • Supported protocols: RT_CLASS_1, RTA, UDP, DCP, ARP, LLDP, SNMP (MIB II)

Connectors and cabling

  • 2 Ports switch (RJ 45)
  • 100 m cable length per switch port
  • Switch delay time: ?? us
  • Auto detect, Auto cross-over, Auto polarity

Backplane

  • Not connected to the PB networks
  • 10 Modules (positioned in the first 10 slots)
  • 410 mA current consumption
  • Power supply: provided through the backplane
  • Compatible backplane units: 101-200011, 101-200012, 101-200023, 101-200024, 101-200027
  • Compatible partner/gateway modules: 101-220210, 101-220110, 101-210210, 101-210110, 101-210010

Others

  • Operating temperature: 0 .. 60 °C
  • Dimensions (LxWxH): 115 x 100 x 25 mm (without backplane)
  • Weight: 111 g
  • Head station firmware: 1.264 and higher
UL listed

Want more information? Ask us.

Marco Bekker NLD, ENG, GER

Marco Bekker

Sales Engineer
T: +31 (0)174 671800

Downloads

All available downloads can be found here

Product card
Datasheet
Manual

Service & Support

FAQ's

Check the most frequently asked questions about ComBricks.

On-site & Online Support

Worldwide PROFIBUS and PROFINET support; on-site and online.

Network Certification

Find out what PROCENTEC can certify in your network.

GSD files

Find and download all the GSD files you need.

Software & Firmware downloads

Request firmware, software and download GSD-files.

Training

  • PROFIBUS Troubleshooting & Maintenance

    11 December 2018, 04 February 2019, 12 March 2019

    The PROFIBUS Troubleshooting and Maintenance training course is fully concentrated on those who install and maintain PROFIBUS installations.

  • FREE ProfiTrace Training

    This free training is concentrated on the number 1 troubleshooting tool for PROFIBUS networks.

  • Certified PROFIBUS Installer

    11 December 2018, 04 February 2019, 12 March 2019

    The Certified PROFIBUS Installer course is essential for electrical engineers and technicians requiring the necessary installation and testing skills for their PROFIBUS DP/PA projects.

Training overview