See "People" page direct lines
Head Station Type 1B with ProfiTrace OE
101-20011B

Head Station Type 1B with ProfiTrace OE

The Head Station is the primary element of ComBricks and has to be inserted in the most left slot of the fixed backplane socket. It schedules the interaction between all modules and provides data storage and an Ethernet interface for the user.

Request offer

Information

Type 1B is an enhanced type that contains a ProfiTrace core for monitoring one PROFIBUS network and an advanced web server for permanent remote maintenance of the PROFIBUS installation over Ethernet (hardware is identical as a type 1A). For monitoring repeater or slave modules are required to provide PROFIBUS telegrams on the backplane network. All modules must be configured on the same network. For more networks see Head Station Type 1C.

Through the ProfiTrace 2 software package, OPC tags can be directly streamed from the Head Station type 1B. ProfiTrace 2 will run with full monitoring functionality and the user can benefit from its features.

The Head Station provides power to all modules through its redundant power supply.

UL-listed

This product is UL-listed. Read more about UL-certification.

Technical specifications

Product features

  • 32 (10 repeater modules positioned in the first 10 slots)
  • Redundant power supply
  • uSD card holder for 32 GB (SD and SDHC)
  • USB connector for firmware updates

Ethernet

  • 10 / 100 Mbps link speed
  • Protocols: HTTP, FTP, SMTP, TELNET, SNMP, CommDTM
  • Ethernet connector: RJ-45
  • Ethernet cable length: max. 100m
  • Ethernet MAC address: 9C.B2.06.xx.xx.xx (label on the side of the Head Station)
  • Ethernet default IP address after reset/purchase: 192.168.1.254
  • Ethernet connections: 20 simultaneous web server clients

Web server with ProfiTrace OE

  • Status of all modules
  • Live List
  • Statistics
  • Message recording
  • Email and log on PROFIBUS events
  • System log

Power supply

  • Operating voltage: 11..26 VDC
  • Backplane current: 2.5 A
  • Current consumption: 800 mA (fully loaded)
  • Power: 20W
  • Reverse polarity protection: Yes
  • Wire diameter: < 2.5 mm2

Relay contact

  • Relay contact resistance: 300 mOhm (plug included)
  • Relay contact current: 0.5A
  • Relay contact voltage: 24 VAC

Backplane

  • PROFIBUS networks: 4
  • Compatible backplane units: 101-200011, 101-200012, 101-200023, 101-200024, 101-200027

Others

  • Operating temperature: 0..60 °C
  • Dimensions (LxWxH): 115 x 100 x 25 mm (without backplane)
  • Weight: 150 g
UL listed

Want more information? Ask us.

Jonathan Machin ENG

Jonathan Machin

Sales Director, Anybus Diagnostics
T: +31(0) 682671130

Downloads

Below you can find the available downloads for this product.

Manual
ComBricks brochure
DWG Drawing
Datasheet
EU Certificate of Conformity

 

Training

  • PROFIBUS Troubleshooting & Maintenance

    06 November 2023, 21 November 2023

    The PROFIBUS Troubleshooting and Maintenance training course is fully concentrated on those who install and maintain PROFIBUS installations.

  • Certified PROFIBUS Installer

    06 November 2023, 21 November 2023

    The Certified PROFIBUS Installer course is essential for electrical engineers and technicians requiring the necessary installation and testing skills for their PROFIBUS DP/PA projects.

  • Certified PROFIBUS Engineer

    06 November 2023

    'Distinguish yourself from the others and show that you are the expert.....Become a Certified PROFIBUS Engineer.'

Training overview